A catalogue describes a product series; a project submittal must match the configuration actually offered. If a generic brochure is used as the basis for approval, it becomes hard to confirm later what was actually delivered.
Link each document to a specific decision
At selection you need the selected datasheet, the applicable performance curve, dimensions, connections and a list of deviations from project requirements. Before assembly, confirm the approved interface drawings. At delivery, check the manual, spare parts data and agreed test records for the actual equipment.
Each row should record the tag number, document title, revision, submittal stage, reviewer and status. Keep “submitted”, “approved” and “as-supplied revision” separate. Check what each certificate covers; a certificate for another model cannot serve as evidence for this equipment.
Close document gaps explicitly
Agree what each test is meant to prove and who reviews it. Passing a technical test does not automatically complete every contractual acceptance obligation. Missing or conflicting documents should have a named owner who follows them up; do not fill the folder with unrelated product literature.
KFE can coordinate document clarification based on your equipment list and submittal schedule. Final approval remains with the reviewer appointed by the project, and the exact evidence required should be agreed in the actual purchase.