How to Specify Movement Requirements for Expansion Joints and Flexible Connectors

A connector can only take the movement and loads it is designed for. The same nominal size does not prove it can absorb thermal expansion, and it should never be assumed to correct installation errors.

State Movements and Restraints

Provide the pipe material, temperature range, layout and the axial, lateral or angular movements set by the design. State whether they occur at the same time, and record pressure, cycles and ambient conditions. Do not simply add together the maximum movement ratings for different directions.

Submit the support, anchor and guide arrangement. Some expansion joints generate pressure thrust, so system restraint needs engineering assessment. A flexible connector does not replace correct alignment and pipe support.

Check the Whole Installation

Request the connection drawing, allowable movements, installed length and operating limits, and check the space and the compatibility of metal or elastomer parts with the real media and temperature. Do not stretch a joint to close a construction gap of unknown origin.

Send KFE the movement schedule and piping drawings and we can coordinate product documents. Pipe stress and restraint design must be approved by the responsible engineer before a solution is accepted.

Related industry: HVAC

Related Products

Send Us Your Equipment List or Operating Conditions

Tell us what you need. KFE handles the quote, specs and delivery, with one contact for you.

Contact KFE